MIL-DTL-62547D
and the extinguisher filled with test liquid. Pressure shall be increased until the relief device
opens [not less than 18,300 kPa (2650 psi) or, more than 20,700 kPa (3000 psi)]. The pressure
shall be recorded.
4.4.2.1.4.2 Pressure indication device. To determine conformance to 3.4.1.4.2, the
following tests shall be conducted. The procedures of 4.4.2.2.4 shall be followed except that the
pressure indicator shall be installed and the pressure maintained at 20,700 kPa (3000 psi) for at
least five seconds. The pressure indicator shall not be damaged, and the pointer, (if used) shall
not be bent. Pressure shall then be returned to ambient. The extinguisher shall be drained and
dried, without cooling, by use of clean filtered air or nitrogen to remove residual moisture. The
extinguisher shall be rebuilt and instrumented with a master pressure gage. The extinguisher
shall be pressurized with nitrogen and cold soaked at 16 °C (5 °F) until the temperature stabilizes
as specified in 4.3.2.2. Nitrogen shall be released through the fill or vent valve until the pressure
reaches 3580 kPa (519 psi). The process shall be repeated at all pressures and temperatures
specified in 3.4.1.4.2.
4.4.2.1.4.3 Pressure switch. To determine conformance to 3.4.1.4.3, the valve shall be
installed on an instrumented cylinder and a charge shall be applied. At ambient pressure the
switch shall be in a normally open position and shall close during charging. Slowly release the
charge through the fill or vent valve and monitor the extinguisher pressure. As the charge is
released, the switch shall open between 2500 and 2200 kPa (363 and 319 psi). The pressure
recession curve shall be as indicated in figure 3.
4.4.2.1.5 Flow indication. To determine conformance to 3.4.1.5, the extinguisher shall
be set up as shown in figure 4. The extinguisher shall be activated by applying a 30 Vdc stop
input across the terminals of the discharge valve. Upon discharge, the flow indication device
shall open a normally closed circuit. A steady state flow indication signal shall be provided
within 5 ms after opening of the valve or the beginning of extinguishant flow. There shall be no
flow indication prior to the beginning of extinguishant flow or opening of the valve. This test
shall be repeated with 16 Vdc and may be conducted concurrently with the test of 4.4.2.1.2.
4.4.2.1.6 Quiescence.
4.4.2.1.6.1 Quiescent/continuity/resistance. To determine conformance to 3.4.1.6, the
resistance in the valve solenoid circuit and in the pressure/flow circuit shall be measured using a
current of less than 5 mA. The resistance shall not exceed 8 ohms.
4.4.2.1.6.2 Continuity/checkout current. To determine conformance to 3.4.1.6, the valve
shall be set up according to figure 5. For qualification testing the discharge valve shall be set up
to take a continuous current flow of 5 mA for not less than 240 hours without activation. This
test may run concurrently with 4.4.5.2.1.1. For quality checks the duration of this test shall be 15
to 30 seconds.
18
For Parts Inquires call Parts Hangar, Inc (727) 493-0744
© Copyright 2015 Integrated Publishing, Inc.
A Service Disabled Veteran Owned Small Business